Permit Number: T22CM07690
Parcel: 113060510

Address:
1915 E LIND RD

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM07690
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2024 Site Zoning APPROVED
02/28/2024 Site Engineering NOT REQUIRED
02/28/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/06/2024 Residential Building REQUIRES RESUBMIT T22CM07690
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

Adding a cooking fixture to the sleeping quarters changes the unit to an ADU type dwelling. All dwellings have many additional requirements which do not apply to the original development of a detached (sleeping quarters) addition.

Provide a complete construction plan set showing 2018 IRC compliance, R106.1.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment.

Show compliance with the Inclusive Home Design Ordinance adopted by the City of Tucson Ordinance #10463 on 10/16/2007. Notate accessible route, minimum door width, changes in floor elevation, door hardware, electrical outlet reach range, grab bar reinforcement, etc.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. Provide a minimum service conductor rating of 100 AMP for the dwelling and conductors with minimum rating of #3 copper 75 degree C, E3602.1 & E3603.1.
2. Update the Riser Diagram showing an appropriate Service Disconnect for each dwelling unit, E3601.6.2.
3. Revise the range circuit size for serving the connected load, E3702.11.
4. Specify high-efficacy lamps for at least 90% of all lighting fixtures, N1104.1. Update note #24.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
01/31/2024 PDSD Application Completeness Express REVIEW COMPLETED