Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - T22CM07641
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/28/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
03/28/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Replacement of commercial AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacity of the unit being installed (Sections C403.3.1 and C403.2.2, IECC 2018). The unit itself will also have to comply with Sections C403.3.2, C403.4 and C403.5, IECC 2018 for efficiency, controls, and economizers. | ||
03/28/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed, the vents for the grease interceptor do not rise 6” above the flood rim of the interceptor (i.e. floor level) prior to rising vertically. [Initial comment: All of the vents must rise vertically to at least 6” above the flood rim of the grease interceptor prior to running horizontally (i.e. no flat venting). Reference: Section 905.4, IPC 2018.] |