Permit Number: T22CM07611
Parcel: 133324610

Address:
9220 E SIMON PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - T22CM07611
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2022 Light Residential Building Review (OIP) APPROVED
11/01/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/01/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM07611


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, R301.1. Show the size and total number and spacing of lag bolts
2. Provide sufficient standoffs for achieving a point load calculation under 45 pounds, R301.1. Show calculation.


BUILDING REVIEW COMMENTS:
Approved
Installation of new PV system onto a flat roof.


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Denied
LABELS 1. Provide the exact wording and location for the “Photovoltaic System Disconnect” marking required by NEC 690.13 (B). 2. Provide the exact wording and location for the “Warning PV Power Source” required by NEC 690.31(G). 3. Provide the exact wording and location for the Power Source “Imp, Vmp, Vmax, Isc, Wmax” marking required by NEC 690.51. 4. Provide the exact wording and location for the “Rapid Shutdown Switch "marking required by NEC 690.56(C)


PLUMBING REVIEW COMMENTS:
N/A