Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/12/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

The previous electrical plan review comments not completely addressed.

1. Comment from the 1st plan review.” Provide a complete electrical line diagram. Show voltage, phase, amp and AIC rating, show all conductor, conduit sizes and types, grounding including connection to the downstream existing equipment.”

Comments from the 3rd plan review.” The original plan review comments are not addressed. . Provide a complete electrical line diagram. Show voltage, phase, amp and AIC rating, show all conductor, conduit sizes and types, grounding including connection to the downstream existing equipment.”

“Revise the electrical plans as necessary and address all the electrical plan review comments. Ref; 2018 IBC section 107.2, 107.2.1, 2017 NEC.”
10/06/2023 PDSD Application Completeness Express REVIEW COMPLETED