Permit Number: T22CM07609
Parcel: 11204275A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM07609
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/02/2022 Commercial Electrical REQUIRES RESUBMIT .Provide a complete electrical line diagram. Show voltage, phase, amp and AIC rating, show all conductor, conduit sizes and types, grounding including connection to the downstream existing equipment. If the electrical service exceeds 400 amps or is tied in with the PV system, provide complete electrical plans, sealed, design and calculations by a registered Electrical Professional registered in the State of Arizona. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements