Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM07609
Parcel: 11204275A

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3

Permit Number - T22CM07609
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/03/2023 Commercial Electrical REQUIRES RESUBMIT The original plan review comments are not addressed.

. Provide a complete electrical line diagram. Show voltage, phase, amp and AIC rating, show all conductor, conduit sizes and types, grounding including connection to the downstream existing equipment. If the electrical service exceeds 400 amps or is tied in with the PV system, provide complete electrical plans, sealed, design and calculations by a registered Electrical Professional registered in the State of Arizona. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements

The comment submitted along with the same electrical plan this submittal states, “We are not changing any wire all wire is being Provided by TEP”. The cover plan Title states, ‘Service Upgrade 150A to 200A and Move to Underground’.

The Details submitted describing the scope of work States,” Relocate SES with Overhaed Service”.

Please address the following electrical plan review comments and provide a written response.

1. It was observed at this plan review that the Registrant seal is expired. Please revise with a current seal.

2. Show the location of where the electrical service was relocated from.

3. The electrical service is increase from 150A to 200A and relocated. How are you not changing any wire as stated?

Revise the electrical plans as necessary and address all the electrical plan review comments.

Ref; 2018 IBC section 107.2, 107.2.1, 2017 NEC.
09/26/2023 PDSD Application Completeness Express REVIEW COMPLETED