Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM07587
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/04/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/04/2023 | Commercial Building | REQUIRES RESUBMIT | 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. structural repair). Reference: Section 107.2.1, IBC 2018. | ||
| 11/02/2022 | Commercial Electrical | REQUIRES RESUBMIT | This project is considered commercial. Please remove all references regarding the IRC and use the currently adopted 2017 NEC, 2018 IECC, 2012 City of Tucson/Pima County Outdoor Lighting Code if applicable. Provide a detailed description in the electrical plan of all the electrical work proposed in order to restore the unit(s) electrical system. Show the location of the electrical panel. If located in the Bathroom or Clothes Closet, relocate to a code approved location. NEC 240.24(D)(E). Ref: 2018 IBC section 107.2.1, 2018 IECC, 2017 NEC, Tucson/Pima County Outdoor Lighting Code. |
||
| 11/01/2022 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. replacement of exhaust fans and HVAC equipment.). Reference: Section 107.2.1, IBC 2018. |
||
| 11/01/2022 | Commercial Plumbing | REQUIRES RESUBMIT |