Permit Number: T22CM07573
Parcel: 119280590

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM07573
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/28/2022 NPPO APPROVED
10/28/2022 Site Engineering APPROVED
10/31/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
10/31/2022 Residential Building REQUIRES RESUBMIT T22CM07573

PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. Place the code reference on the plans.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

SITE PLAN:

Provide a site plan showing the location of the electrical service panel.

FLOOR PLAN:

Provide a floor plan showing each proposed room with labeled function and dimensions.

PLUMBING PLANS:

Provide piping (supply, drains and vents) locations and code compliant sizes.

MECHANICAL PLANS:

Provide equipment details showing code compliant components, locations and sizes of a HVAC.

ELECTRICAL PLANS:

Provide proposed wiring details showing code compliant device locations and circuit sizes. Show circuit number and size with receptacles at all walls (within 6’ of any wall location) and lighting control at each doorway both interior and exterior. Receptacle, lighting and smoke detector circuits require arc-fault protection, E3902.16.

Show at least one wall switch controlled light or outlet in bathrooms, hallways, outdoor entrances or exits and all habitable rooms, E3903.3.

Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.

Show GFCI protection at sink locations, E3902.6.

INTERNATIONAL ENERGY CONSERVATION CODE:

Provide insulation details (existing or proposed) minimum (R-13 walls and R-30 small additions or otherwise R-38 ceiling) showing code compliant placement of materials and ratings, N1101.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

PLEASE NOTE: Planning and Development Services launched Tucson Development Center Online on Monday, October 31. TDC Online is a self-service portal that will provide transparency throughout the permitting process. To sign up for an account and submit an application, visit https://tdc-online.tucsonaz.gov
10/28/2022 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM07573
Addition
2536 W RUTHANN DR Zoning R-1

TRANSMITTAL DATE:?October 13, 2022


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1.COMMENT: Provide a Residential Plot Plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf This shall in include:
a. Lot coverage calculation that meets the requirements of UDC Article 6.4.3 & the example shown on the residential plot requirements. (Lot coverage must include vehicular use area whether improved or unimproved)
b. Zoning of adjacent parcels
c. All Utility lines
d. Property line distances

2.COMMENT Clearly show everything on site. Based on current aerial photos there is an unpermitted addition on the rear of the house. Additional comments may be forth coming.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov