Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T22CM07532
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/22/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/22/2024 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The air balance report shows multiple exhaust fans and rooftop units unable to be balanced to within +/- 10% of the design airflow rates for ventilation and air distribution. The engineer of record shall review the situation and determine the course of action prior to the air balance report being resubmitted. Reference: Section 403.3.1.5, IMC 2018. | ||
02/21/2024 | PDSD Application Completeness | REVIEW COMPLETED |