Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM07445
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/28/2022 | Site Zoning | APPROVED | |||
| 11/09/2022 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 11/09/2022 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide a metering faucet for the relocated lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the faucet cycle will last for at least 10-seconds. Reference: Section 419.6, IPC 2018, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09. 3. Provide tempered water for the relocated lavatory using an approved device conforming to ASSE 1070. Reference: Sections 419.5 and 607.1.2, IPC 2018. 4. Verify that the distance from the hot water source to the hot water termination for the relocated lavatory complies with the requirements of Section C404.5, IECC 2018 (e.g. 24” for a ½” supply, see Table C404.5.1, IECC 2018). |
||
| 10/28/2022 | External Reviewers - SAFEBuilt | REQUIRES RESUBMIT | {Activity date: 10/03/2022; Status: Reqs Change; Reviewer: DBENOIT1; Title: COMMERCIAL - BLDG/FIRE/ZONING/ENG; Comment: Activity Number: T22CM07445GENERAL: Provide written responses to all review comments.Provide a complete plan set.Provide additional documents as requested by review staff.STRUCTURAL REVIEW COMMENTS:Denied1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents. Plan review stopped due to incomplete plans.BUILDING REVIEW COMMENTS:Denied1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.Plan review stopped due to incomplete plans. MECHANICAL REVIEW COMMENTS:Denied1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.Plan review stopped due to incomplete plans.ELECTRICAL REVIEW COMMENTSDenied1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.Plan review stopped due to incomplete plans.PLUMBING REVIEW COMMENTS:Denied1. Indicate on plans correct code years in "Code Data and Square Footage" city is on 2018 ICC code family and 2017 NEC.2. Plans indicate Basic Wind Speed of 90MPH - Tucson indicates: Section 1609.1.1 Determination of wind loads. REVISE Section by ADDING the following after the last paragraph: Per the Basic Wind Speed Figures, use the following: Risk Category I – 100 mph Risk Category II – 105 mph Risk Category III – 110 mph Risk Category IV – 115 mph - Correct plans3. Title sheet indicates electrical plans; however, no electrical plans in submitted documents.Plan review stopped due to incomplete plans.If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov} | ||
| 10/28/2022 | Fire New Construction | REQUIRES RESUBMIT | {Activity date: 10/04/2022; Status: Reqs Change; Reviewer: JPEELDA1; Title: COMMERCIAL - BLDG/FIRE/ZONING/ENG; Comment: Plans reference the wrong ICC code books. We are in the 2018 code cycle. Please updatePlans shall show if the building has fire sprinklersBuilding address shall be shown on the plans and compliant with the TFD address requirements found on our website under permits and resources for amendments.Questions:Jennifer Peel-DavisJennifer.Peel-Davis@Tucsonaz.gov520-837-7033Fire Plans ExaminerTucson Fire Department} | ||
| 10/28/2022 | Site Engineering | REQUIRES RESUBMIT | 1. With the proposed modification of the existing trash enclosure a Development Package will be required that shows the new trash collection maneuverability and that the trash enclosure is built per code (Technical Standards Manual section 8).Stephen Blood(520) 837-4958Stephen.blood@tucsonaz.gov |