Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2023 Site Zoning APPROVED
03/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2023 Residential Building REQUIRES RESUBMIT PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

SECTIONS - DETAILS:

1. Show a complete cross-section detail of the new exterior wall, R106.1.1. Show the continuous #4 rebar reinforced footing, R403.1. Show the wall assembly with a 6” clearance above the ground or 2” clearance above an exterior concrete surface, R317.1 item 5.

2. Show roof (uplift resistance) fasteners (H2.5) with appropriate uplift capacity, R802.11 amended.

3. Eave ventilation is not appropriate without attic space, or rafter cavity space between insulation and roof sheathing, R806.1. Remove the “vent” notation at wall keynote #3.

ELECTRICAL PLANS:

1. Smoke alarms are required outside each separate sleeping area, R314.3.2. In addition to the bedroom also show an alarm outside the doorway in the immediate vicinity.