Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM07372
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/29/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/29/2022 | Commercial Electrical | REQUIRES RESUBMIT | It is City policy for all new electrical service conductors to be installed underground unless already overhead exists to the building, per 2018 IBC Amendments section 112.1.1. Because the scope of work calls for changing the existing Utility conductors from underground to overhead. The applicant will need to file an Appeal to the Building Official for a variance to the Code. The underground service waiver form can be downloaded from www.tucsonaz.gov/pdsd website. |
||
12/22/2022 | PDSD Application Completeness | REVIEW COMPLETED |