Permit Number: T22CM07308
Parcel: 11610002B

Address:
2202 W ANKLAM RD

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM07308
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2022 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/01/2022 Commercial Plumbing REQUIRES RESUBMIT 1. Specify the materials of construction for the building sewer and the new vent. Reference: Section 702.3, IPC 2018.
2. Show the location of all cleanouts for the building sewer. The maximum distance between cleanouts shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Sections 703.5 and 708.1.1, IPC 2018
3. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Section 708.1.8, IPC 2018
4. Cleanouts shall open to allow cleaning in the direction of flow (keynote 1, downstream of existing 3” sewer line). Reference: Section 708.1.8, IPC 2018.
5. The installation of building traps is prohibited (Detail A1/CU501). Reference: Section 1002.6, IPC 2018.