Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - T22CM07289
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/23/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/23/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review T22CM07289 (4818 E 12TH ST TUCSON, AZ 85711) The provided plans show the removal of the derated MS breaker and an allowable backfeed of 80A (Sheet ELECTRICAL 3LD). 111A PV source is greater than the 80A allowable backfeed. The following updates are required: 1. Provide documentation showing the Bus rating for each segment of the PV connected bus. (Sheet ELECTRICAL 3LD, left side of MSP with 200A MS breaker). 2. Provide code references justifying 111A PV backfeed. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |