Review Details: RESIDENTIAL SOLAR v.1
Permit Number - T22CM07289
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/10/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/10/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | NOTE: Being that this application for a permit is not yet an Approved building permit, revision to this permit should not as of yet exist. You have already submitted 4 revisions to this permit application which is causing confusion. Please Do Not submit revisions until this permit has been approved as building permit should it be required, just upload the drawings as correction to the current permit Application. Please respond to the following: 1. Protection to Sub Panel is required, please install a main breaker. 2. Install the correct conductor size on both side of the tap corresponding to the large AMP coming from both the PV system and utility. 3. Please have a licensed Electrical Engineer who is a registrant licensed in Arizona review/seal/sign these PV drawings. Please make sure that he/she fully coordinate this PV design to a coherent system. 4. Please resubmit. |
||