Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - T22CM07142
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/08/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 03/08/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review T22CM07142 Verify TEP has approved location of 200A MSP in relationship to DG disconnect switch. TEP SR-702 (b) requires DG disconnect switch to be within 10’ of customers revenue meter. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |