Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - T22CM06827
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/21/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken. OCPD for copper conductor may not exceed 35 A for a 10 AWG conductor, NEC Table 310.15(B)(16) 75 degree C, NEC 230.90(A). The conductor tagged #3, between the disconnect and ConnectDER, on page PV-4.0 is undersized for the 60A PV Breaker in the ConnectDER Meter Adapter. | ||
| 07/03/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |