Permit Number: T22CM06827
Parcel: 120022000

Address:
4425 S 16TH AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - T22CM06827
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/21/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated plans and calculations with a written response to each of the notated items indicating action taken. OCPD for copper conductor may not exceed 35 A for a 10 AWG conductor, NEC Table 310.15(B)(16) 75 degree C, NEC 230.90(A). The conductor tagged #3, between the disconnect and ConnectDER, on page PV-4.0 is undersized for the 60A PV Breaker in the ConnectDER Meter Adapter.