Permit Number: T22CM06756
Parcel: 110090010

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.5

Permit Number - T22CM06756
Review Name: RESIDENTIAL NEW DWELLING v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
11/13/2024 Site Engineering REQUIRES RESUBMIT 1. The drainage plan doesn't look right, the natural contours of the site indicate that the site drainage will head north, northeast, and northwest and not toward E Fort Lowell Rd. Revise as needed and show the positive drainage away from the building foundation along with roof drainage (which will be the only concentrated flow onsite due to the flat nature of the property).

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
11/14/2024 Site Zoning REQUIRES RESUBMIT See Engineering comments
11/07/2024 Historic REVIEW COMPLETED Based on staff review of the resubmitted site plan and construction plan set against the settlement conditions within Ordinance No. 12120, the following conditions must be addressed and satisfied prior to approval of T22CM06756. Historic staff has reviewed revised plans submitted on 10/25/2024 to ensure all outstanding conditions are addressed as requested. The supplemental drainage plan has not been assessed by this reviewer, deferring to Engineering staff.

Condition 5: The applicant shall submit a preservation drainage plan to protect the existing adobe ruins by preventing erosion and provide a note on the plans showing how the ruins will be protected during construction by directing drainage away from the ruins and showing construction fencing without major ground penetration. This plan and the corresponding note will be reviewed by City staff for compliance.

Comment: Submit a supplemental drainage plan demonstrating how the existing adobe ruins will be protected from erosion. A note should also be placed on the construction plan set showing the drainage being directed away from the ruins during construction of the dwelling. Please note the supplemental drainage plan will be reviewed by City Engineering staff.
DEFER TO ENGINEERING STAFF FOR COMPLIANCE-needs review comments
Condition 6: The plans will provide additional information on the steps in the design regarding the long-term preservation and protection of the ruins. This additional information will be reviewed by City staff for compliance and approval, which approval if issued and accepted by applicant shall be final.

Comment: Submit a supplemental preservation plan demonstrating the long-term preservation and protection of the ruins. City staff recommends consulting a professional with knowledge and experience with adobe preservation to satisfy this condition.
DEFER TO ENGINEERING STAFF FOR COMPLIANCE-needs review comments
Condition 7: An elevation installation detail for the long-term fencing for the ruins, noting materials, is provided on the plans.

Comment: Provide a detail within the construction plan set of the proposed permanent fencing surrounding the ruins. Ensure the detail notes the materials of the long-term fencing.
COMPLIES AS SHOWN ON SHEET A 106

Condition 9: The location of the property line and adobe perimeter wall shall be accurately depicted on the revised site plan.

Comment: Draw the location of the adobe perimeter wall on the site plan, even though this wall is not located within the development.
COMPLIES AS SHOWN ON SHEET A100
Condition 14: The applicant shall remove or relocate old chain link construction fencing that is in the Fort Lowell right-of-way.

Comment: While the comment response letter indicates the old chain link construction fencing has already been removed, show its former location on the site plan and provide a note stating this fencing has been removed.
COMPLIES SEE SHEET A100
Condition 15: The applicant shall show existing equestrian trail easement on the site plan.

Comment: The site plan shows a 30-foot-wide ingress/egress and utility easement but does not specifically reference an equestrian easement. Modify the notation relating to the 30-foot-wide easement if this easement also serves as an equestrian easement.
COMPLIES SEE SHEET A100
Condition 20: Foundation surfaces shall match building stucco, flush stucco to grade.

Comment: Include notations on both the site plan and elevation drawings that the foundation surfaces will match the building stucco and be flush stucco to grade.
COMPLIES SEE SHEET A100 AND A105
Condition 21: Lot will not be covered with DG.

Comment: Add a note on the site plan stating that the lot will not be covered or surfaced with decomposed granite.
COMPLIES SEE SHEET A100
Condition 22: Drainage must be designed so it will not impact ruins or adjacent properties down slope to the east and north.

Comment: The supplemental drainage plan must show the drainage will not impact the existing adobe ruins or adjacent properties to the east and north. Please note the supplemental drainage plan will be reviewed by City Engineering staff.
DEFER TO ENGINEERING STAFF FOR COMPLIANCE-needs review comments
Condition 23: Double hung or casement windows, bronze, aluminum clad are acceptable, if they mimic wood windows. If aluminum, set to the inside face of the wall.

Comment: Provide a window schedule within the construction plan set demonstrating compliance with the above window specifications.
COMPLIES SEE SHEET A106
Condition 24: Color of the stucco shall be similar to the color of the adobe ruins, as reasonably practical, same color as the ruins or darker.

Comment: Include a photo of the existing adobe ruins within the construction plan set, and provide a color detail demonstrating that the stucco on the new construction will match or be darker than the ruins.
COMPLIES SEE SHEET A106
Condition 25: Permanent three-foot corral fence shall be erected around the west, south, and east perimeter ruins.

Comment: Notate the location of the permanent three-foot corral fence on the site plan.
COMPLIES SEE SHEET A100
Note: Engineering review comments MUST be provided prior to any final approval.
Any question on comments on historic contact Michael.Taku@tucsonaz.gov
10/25/2024 PDSD Application Completeness REVIEW COMPLETED