Permit Number: T22CM06657
Parcel: 107132110

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM06657
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2022 Residential Building REQUIRES RESUBMIT T22CM06657
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Each dwelling unit with kitchen requires a separate Pima County assigned street address, R319. Notate each dwelling address on the site plan (or remove cooking appliances).

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electric and sewer or septic lines from property line to building, R106.1.1. Identify the utility lines requiring upgrade or replacement.
2. Show a street address for each dwelling on the site plan, R319.
3. Show the dimension to property line. Exterior walls with a fire separation distance less than 3-foot to the neighboring property line require not less than one-hour fire-resistive construction. Show compliance with R302.1 (City of Tucson Amended) by providing a section detail of materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.

PLANS:

1. Notate a cool (white) roof finish as required by the ADU provisions.

SECTIONS - DETAILS:

1. Show one-hour fire-resistive framed construction separating dwellings in compliance with IBC Table 721.1(2).
2. Show a cross-section detail for the garage door opening closure. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5) with minimum ½” diameter anchor bolt and treated sill plates, R602.10.8 & R403.1.6. This may require a concrete stem when the floor is less than 6” above grade.
3. Show an unvented roof assembly with all insulation at the roof including an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing as part of the total insulation requirement, R806.5.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.
2. Show the water heater location for the dwelling unit, P2801.1.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation, or controlled exhaust with a calculated airflow rate, R303.4; N1103.6 & M1505.4. Show the system and appropriate flow rate setting on the plans. A one bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. Provide a minimum service conductor rating of 100 AMP for each dwelling and conductors with minimum rating of #4 copper 75 degree C, E3602.1 & E3603.1. Update the Riser Diagram showing the correct feeder size.
2. Clarify the Riser Diagram to show if the service panel is upgraded with a 400 AMP service, NEC 225.30 and E3403.
3. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
4. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901..6.
5. Update the panel schedule for a water heater circuit and notate a disconnect means or a locking breaker for the water heater, E4101.5.

OUTDOOR LIGHTING CODE

1. Show the proposed fixture as full cut-off FCO style or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining exterior lighting limits.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review
11/01/2022 Site Zoning REQUIRES RESUBMIT FROM: Iman Monshizadeh

PDSD Zoning Review Section

PROJECT: T22CM06657 / ADU

Plot Plan Review (1st Review)

2641 N FONTANA AV / R-2 Zone

TRANSMITTAL DATE: 09/01/2022



Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.



1.COMMENT: Provide setback dimensions from the ADU to the north and west property line. Setbacks for the interior property lines in an R-2 zone are 6’ or 2/3* Height (whichever is greater). If Setbacks are not met a Design Development Option (DDO) will be required to reduce setback dimensions. Contact Mark Castro at Mark.Castro@tucsonaz.gov or by phone at 520 837-4979 for more information regarding DDOs.



2.COMMENT: Show a dedicated parking space for the ADU.

3.COMMENT: Lot coverage calculation for the existing residence shall include vehicle use areas including the driveway.



All required information regarding ADUs can be found at: https://www.tucsonaz.gov/files/pdsd/projects/ADUs/CASITA_Worksheet_22.01.06_WEB.pdf





For questions regarding Zoning comments, please contact me at: Iman.Monshizadeh@tucsonaz.gov

To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp
11/01/2022 Bldg Permits - Post Review Express REVIEW COMPLETED