Permit Number: T22CM06642
Parcel: 125101350

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM06642
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/15/2023 Commercial Electrical REQUIRES RESUBMIT Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.
1 Provide site lighting plans with the following information on the plans;
Provide a complete luminaire schedule.
2 Size of the parcel in acres.
3 See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing.
4 402.1 (light source color temperature requirements), shielding requirements, etc .
5 Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1.
6 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.
7 Specify any exceptions used.
8 Curfew lighting controls If applicable.
Do not confuse the Outdoor Lighting Code with the IECC.
9 Show wiring methods, branch circuit and panel designations per 2017 NEC.
Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
01/31/2023 PDSD Application Completeness REVIEW COMPLETED