Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - T22CM06642
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/15/2023 | Commercial Electrical | REQUIRES RESUBMIT | Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements. 1 Provide site lighting plans with the following information on the plans; Provide a complete luminaire schedule. 2 Size of the parcel in acres. 3 See table 401.1, lighting area and option and indicate this information in the lighting site plan, also showing the locations and types of all exterior luminaires including existing. 4 402.1 (light source color temperature requirements), shielding requirements, etc . 5 Provide calcs for total lumens allowed and total lumens proposed per acre including existing, for Full Cut Off and Unshielded per table 401.1. 6 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 7 Specify any exceptions used. 8 Curfew lighting controls If applicable. Do not confuse the Outdoor Lighting Code with the IECC. 9 Show wiring methods, branch circuit and panel designations per 2017 NEC. Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC. |
||
01/31/2023 | PDSD Application Completeness | REVIEW COMPLETED |