Review Date Reviewer's Name Type of Review Description Status Comments
03/14/2023 Commercial Electrical APPROVED
03/14/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/21/2023 Commercial Mechanical REQUIRES RESUBMIT The submitted drawing set does not include sheet M1.01 but has two copies of M0.00 and a blank copy of M0.14. [Third comment: The submitted drawing does not include the air distribution revision noted in the response to comments dated 01/13/2023.] [Second comment: Comment not addressed.] [Initial comment: The mechanical plan shows a high velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.]
02/16/2023 PDSD Application Completeness Express REVIEW COMPLETED