Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - T22CM06357
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2023 | Commercial Electrical | APPROVED | |||
03/14/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/21/2023 | Commercial Mechanical | REQUIRES RESUBMIT | The submitted drawing set does not include sheet M1.01 but has two copies of M0.00 and a blank copy of M0.14. [Third comment: The submitted drawing does not include the air distribution revision noted in the response to comments dated 01/13/2023.] [Second comment: Comment not addressed.] [Initial comment: The mechanical plan shows a high velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.] | ||
02/16/2023 | PDSD Application Completeness | REVIEW COMPLETED |