Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - T22CM06357
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/13/2023 | Commercial Plumbing | APPROVED | |||
02/13/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/01/2023 | Commercial Electrical | REQUIRES RESUBMIT | Panel ‘A1’ is protected by a Main Circuit Breaker. Provide overcurrent protection for panel ‘A2’ as required per NEC 408.36(B), or verify that it protected per NEC 240.21. Ref; 2018 IBC section 107.2.1, 2017 NEC |
||
02/13/2023 | Commercial Mechanical | REQUIRES RESUBMIT | The submitted drawing does not include the air distribution revision noted in the response to comments dated 01/13/2023. [Second comment: Comment not addressed.] [Initial comment: The mechanical plan shows a high velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.] | ||
01/24/2023 | PDSD Application Completeness | REVIEW COMPLETED |