Permit Number: T22CM06357
Parcel: 137056160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - T22CM06357
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/13/2023 Commercial Plumbing APPROVED
02/13/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/01/2023 Commercial Electrical REQUIRES RESUBMIT Panel ‘A1’ is protected by a Main Circuit Breaker. Provide overcurrent protection for panel ‘A2’ as required per NEC 408.36(B), or verify that it protected per NEC 240.21.

Ref; 2018 IBC section 107.2.1, 2017 NEC
02/13/2023 Commercial Mechanical REQUIRES RESUBMIT The submitted drawing does not include the air distribution revision noted in the response to comments dated 01/13/2023. [Second comment: Comment not addressed.] [Initial comment: The mechanical plan shows a high velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.]
01/24/2023 PDSD Application Completeness REVIEW COMPLETED