Permit Number: T22CM06357
Parcel: 137056160

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM06357
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/12/2022 Commercial Electrical REQUIRES RESUBMIT Previous electrical plan review comments not addressed.
01/10/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Comment not addressed. [Initial comment: Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. all of the air supplied to each restroom is to be exhausted during the hours of operation even if the lights are off). Reference: Section 403.2.1 (4), IMC 2018.]
2. Comment not addressed. [Initial comment: Per Table 403.3.1.1, IMC 2018, the occupant load for a dining area is 70 people per 1,000 square feet. Revise the occupancy load used for the dining area based on Table 403.3.1.1, IMC 2018, or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3.1.1, IMC 2018.]
3. Comment not addressed. [Initial comment: Coordinate the outside air provided by RTU-1 in note #2 of the Ventilation Compliance table (100 CFM) with the results of the Ventilation Compliance calculation (280 CFM), the Kitchen Air Balance table (80 CFM), and the BOH Air Balance table (200 CFM). Reference: Section 107.2.1, IBC 2018.]
4. Comment not addressed. [Initial comment: Show that the hood installation complies with Section 507.2.6, IMC 2018 with regard to a smooth, cleanable, non-absorbent, and non-combustible material installed between the hood and the wall behind the hood and extending 18” beyond the hood.]
5. Comment not addressed. [Initial comment: The mechanical plan shows a high velocity diffuser in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.]
01/10/2023 Commercial Plumbing REQUIRES RESUBMIT The hot water supply to the lavatory in Restroom 104, as shown on plan 1/P1.01 and isometric 2/P1.01, does not comply with the requirements of Section C404.5, IECC 2018. The hot water supply to the lavatory in Restroom 105, as shown on plan 1/P1.01 and isometric 2/P1.01, does comply with the requirements of Section C404.5, IECC 2018. [Initial comment: Verify that the distance from the hot water source to the hot water termination for the public lavatories complies with the requirements of Section C404.5, IECC 2018.]