Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM06354
Parcel: 13734001D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM06354
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2022 Commercial Plumbing APPROVED
10/31/2022 Site Engineering APPROVED
10/31/2022 Site Zoning APPROVED
11/07/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/07/2022 External Reviewers - SAFEBuilt PENDING ASSIGNMENT Activity Number: T22CM06354

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Conditionally Approved
1. Separate tenant improvement drawings shall be submitted by others showing compliance with Sections 2902.3 and 2902.3.1. Reference to storage and retail spaces have been removed from the plan and a note is added at general note #39.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/07/2022 Fire New Construction PENDING ASSIGNMENT Denied
1. Sheet A1.0: The exit separation distance is measured incorrectly. Additionally, the measurement provided is not measured between two exits. Provide a correctly measured exit separation distance in accordance with Section 1007.1.1.1.
2. Sheet A1.0: The construction type listed is incomplete. Provide a corrected construction type in accordance with Chapter 6.
3. Sheet A1.0: The occupancy group provided doesn't match the occupancy groups on the egress plan. Provide a corrected occupancy class and a narrative as to the use of the space.
4. Sheet A1.0: Provide clarification about the adjacent tenant to ensure proper tenant separation.
5. Sheet A1.0: There are spaces that have not been counted in the occupant load calculation. Provide a space load calculation in accordance with Section. 1004.3.

Questions:

Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
Tucson Fire Department
10/31/2022 External Reviewers - Pima County Addressing REQUIRES RESUBMIT Unit # needed prior to issuance. You may contact Pima County Addressing Phone #:520-724-9512 Email: addressing@pima.gov