Permit Number: T22CM05879
Parcel: 10408078B

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM05879
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2024 Water - PDSD APPROVED
07/16/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/17/2024 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Structural(S) Reviewer
Madeline Nelson
mnelson@safebuilt.com
Denied
Reason:
Date Completed : 6/14/2024 2:28:21 PM
1. S101 - MISSING DETAILS: New Foundation Plan Note 36 on Sheet S101 refers to Detail 118 for additional
information on fascade wall framing. The most recent version of Detail Sheet S301 available, dated 7/22/22, does not include a Detail 118. Please provide the missing detail or resubmit Sheet S101 with a revised section callout.

2. S102 - MISSING/INCORRECT DETAILS: Revised 2nd Floor Framing Plan, S102, includes section callouts on Gridline 5 referencing Detail 243 and 250. The most recent version of Detail Sheet S403, dated 7/22/22, does not include a Detail 250. Further, Detail 243 appears out of date with the recent revisions to the entryway. Please provide the missing details or resubmit Sheet S102 with revised section callouts.
07/08/2024 Site Engineering REQUIRES RESUBMIT See zoning comment
07/02/2024 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: T22CM05879 – DP22-0170
700 W Auto Mall Dr – C-3
New Auto Sales Building – (Revision 1st Review)

TRANSMITTAL: July 2, 2024

This site is located in C-3 Zone (UDC Article 4.7.22). Auto sales is a permitted use (UDC Table 4.8-4), subject to Use Specific Standards 4.9.9.G.1& .2.

1. Sheet A110 the landing called out under Keynote 38 does not match what is shown on DP22-0170. A revision to the DP is required and must be approved by all review agencies prior to approval of this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/15/2024 Fire New Construction REVIEW COMPLETED
06/11/2024 PDSD Application Completeness REVIEW COMPLETED