Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T22CM05859
Parcel: 140360170

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM05859
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2023 External Reviewers - SAFEBuilt APPROVED Activity Number: T22CM05856 T22CM05857 T22CM05858 T22CM05859

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditinally Approved
Approved/subject to field approval

ELECTRICAL REVIEW COMMENTS
Conditinally Approved
E4.1:Would suggest Architect rename Pool Yard room 424 to something more appropriate when this room has the SES-C switchboard.
Should state than Panels C and P (Pool) are on Sheet E4.4
E4.2: Should have emergency lighting in Bath rooms, Café and Game room.
E4.5: Fault current calculation for F3 mislabeled as a 2nd F2.
E6.1: Panel DW shall be NEMA 3R.
E7.2: Pool, electrical room, and bathrooms should all have emergency lighting.


PLUMBING REVIEW COMMENTS:
Conditinally Approved
Third Plumbing Review: OK Subject To Field Inspections
1).OK
2). Ok
3). OK -Clubhouse gas BBQ's on P4.4 need exhaust hoods above due to being below structure shown on plan pages A4.0 &
A4.3 -IFGC 623.5 **Plan page A4.3 Revised Open air above BBQ**
4). OK- Ramada gas BBQ's on P3.0 need exhaust hoods above due to being below structure shown on plan pages A3.1 -IFGC 623.5 **Plan page A3.1 Revised Open air above BBQ**
5). OK -Outdoor sink on plan page P3.0 can't receive storm water. -IPC 1101.3 ** Plan Page P3.0 Added Sink Cover **
6). OK
7).OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/14/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
03/14/2023 Site Engineering REQUIRES RESUBMIT See zoning comment
03/14/2023 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM05856, T22CM05857, T22CM05858 & T22CM05859
5125 E Valencia Crossing Dr. – PAD-21 - (1st Review)

TRANSMITTAL: March 14, 2023
This site is located in PAD-21.

1. Zoning has reviewed the building plans for compliance with DP22-0038 and although the building plans appear to match the DP in regard to building shape, size and height Zoning cannot approved the building plans until the DP is approved and the following comment is addressed.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.