Permit Number: T22CM05813
Parcel: 125075530

Address:
333 N WILSON AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM05813
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2022 Fire New Construction APPROVED
12/30/2022 NPPO APPROVED
12/30/2022 Site Engineering APPROVED
01/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/30/2023 Residential Building REQUIRES RESUBMIT T22CM05813
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

PLANS:

1. Provide manufacturer’s calculations and data for pre-engineered trusses dated and wet-sealed by an engineer who is registered in Arizona, or notate the requirement for deferred submittal, R106.1.

SECTIONS - DETAILS:

1. Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation or need for providing air-impermeable rigid insulation at the roof, R806.
2. Attic space requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5.

PLUMBING PLANS:

1. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate yard pipe bypassing the existing dwelling and the water meter size.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/S/D standards, M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D. Notate if the mechanical plans if system calculations will be provided by deferred submittal.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Energy Certificate: (Mandatory) place near the indoor furnace or in utility room, N1101.14. Add notation to plans.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
(520) 837-4912 PDSD-Residential@tucsonaz.gov
01/12/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: T22CM05813
333 N WILSON AV - R-1
Addition w/Demo

TRANSMITTAL DATE: January 12, 2023


COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. This comment was not addressed. At this time Historic Review section, Jodie Brown, has not received any documentation for the demo review. COMMENT: The Pima County Assessor’s effective construction date for your building or structure is 1948. The actual construction date may be earlier. Buildings, portions of buildings or structures that are 50 years of age or older must be architecturally documented prior to demolition. Documentation will be reviewed and approved by the Historic Preservation Office before a permit is issued. Demolition (Historic and Older Structures) Application and General Information may be downloaded (PDF) at https://www.tucsonaz.gov/pdsd/all-application-forms-submittal-requirements. Return completed documentation to PDSDHistoric@tucsonaz.gov. Applicant will be contacted within 5 working days if additional materials are required for review.

2. This comment was not fully addressed. Clearly show the 8’-6” parking spaces on the plan, including in the garage and under the carport and demonstrate that the dust control requirement is met for the area under the carport. COMMENT: Clearly show everything on site. Clarify if the existing metal structure to the northwest is to be removed additional comments may be forthcoming. COMMENT: Show parking per Use Specific Standards 4.9.7.B.7 which states “For any new single-family dwelling in the R-1 zone with five bedrooms, three parking spaces are required. For every bedroom over five, one additional space is required for each bedroom. For all single-family dwellings in the R-1 zone with five or more bedrooms, and for all lots containing two or more single-family dwellings, with the second dwelling having more than one bedroom, all parking spaces must be located on-site, either in a side or rear perimeter yard. Parking spaces may not be located in a vehicular use area in any front street perimeter yard. A parking area is not required to be developed to a commercial standard. A dustproof parking surface is required to at least a minimum of two inches of compacted pea gravel. An existing covered residential parking area may be used.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
12/30/2022 PDSD Application Completeness Express REVIEW COMPLETED