Permit Number: T22CM05741
Parcel: 135083470

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - T22CM05741
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2023 Site Landscape APPROVED
02/21/2023 Site Zoning APPROVED
02/21/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2023 Residential Building REQUIRES RESUBMIT Permit Review T22CM05741

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

Structures built without a permit may require alteration for building code compliance.

Electrical Review
1. Construction documents shall provide information on wiring methods, circuiting and electrical load calculations which demonstrate that the premises electrical system has load capacity to accommodate the added load. IRC E3701 – E4101.
2. Show size and ampacity rating of all conductors from the “Exist 100A panel” to all fixtures, outlets and devices in the shed. Table E3702.14
3. Show HVAC Electrical specs. Confirm conductor is sized correctly.
4. Provide conduit size and depth from Exist 100A panel to panel in shed.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov