Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T22CM05472
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/26/2023 | Special Inspection Certificate Review (Deferred Submittal) | APPROVED | |||
05/26/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/26/2023 | Air Balancing/Commissioning Report (Deferred Submittal) | REQUIRES RESUBMIT | The air balance report shows that EF-2 is not able to achieve the minimum exhaust flow rate required by Table 403.3.1.1, IMC 2018. Correct the deficiency and resubmit the report. Reference: Sections 403.3.1.2 and 403.3.1.5, IMC 2018. |