Review Date Reviewer's Name Type of Review Description Status Comments
05/26/2023 Special Inspection Certificate Review (Deferred Submittal) APPROVED
05/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/26/2023 Air Balancing/Commissioning Report (Deferred Submittal) REQUIRES RESUBMIT The air balance report shows that EF-2 is not able to achieve the minimum exhaust flow rate required by Table 403.3.1.1, IMC 2018. Correct the deficiency and resubmit the report. Reference: Sections 403.3.1.2 and 403.3.1.5, IMC 2018.