Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM05467
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/06/2023 | Commercial Mechanical | APPROVED | |||
06/07/2023 | Site Zoning | APPROVED | Legacy Approval by STEVE SHIELDS | ||
07/06/2023 | Water - PDSD | APPROVED | |||
07/10/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
07/10/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous electrical plan review comments are not completely addressed. Show breaker panel location. Verify that the adding or relocating of partitions does not render the breaker panel in a non-code compliant location. See NEC art 240.34(D), (E). If the panel is in any of these locations please relocate. Any replaced receptacles shall be tamper resistant and AFCI protected as required per NEC 210.12(D), 406.4(D). This project is considered commercial. Remove references to the IRC and revise to 2017 NEC. Verify that the bathroom receptacles are dedicated 20 amp branch circuits as required per NEC art 210.11(C)(3). Replaced luminaires shall comply with the 2018 IECC section R404. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
07/06/2023 | Commercial Plumbing | REQUIRES RESUBMIT | Note requiring third-party listing of plumbing fixtures not found. [Initial comment: Specify that all proposed plumbing fixtures shall be listed by a third-party certification agency as complying with the relevant standards. Reference: Section 303.4, IPC 2018.] | ||
06/13/2023 | External Reviewers - Willdan | REQUIRES RESUBMIT | Activity Number: T22CM05467 Building & Structural Review GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. Sheet 1 Provide Building Type. Provide Occupancy Type. Provide Occupancy Load. Provide Exiting Plan. Sheet 1 Provide comment letter response to all items noted. Additional comments may follow when requested information is provided. Sheet 2 Provide Structural Engineering for Masonry openings and demolition. Provide complete framing plan for new walls and doors ways. Provide path of travel to the public way per IBC and ADAAG. Provide exit signs per the IBC. Provide slab repair details for plumbing trenches. Sheet 5 Provide complete details of bathroom regarding ADA. per ADAAG Sheet A! Per IBC Section 308, the architect needs to identifyGroup I-1 as either Condition 1 or Condition 2. Sheet A31. Identify the size of the egress door. 2. Provide a landing and path of travel to the public way that complies with ADAAG and ICC A117. Show it on the site plan.3. Provide a Accessible Parking stall to ADAAG and ICC A117. ( I-1 Occupancy) Sheet A3 Provide wall framing details, Show attachment to existing structure. Sheet A3 Show door sizes and Accessible hardware. Sheet A3 Will the unit 1 be accessing unit 2? Are there any modifications to unit 2? Sheet A3 The bathroom layouts appear to have changed from the First Review. All Changes or Deletions shall be either clouded or highlighted. The plans have been modified in both unit 1 and unit 2. Sheet A3 Provide a minimum 1 ADAAG Compliant Bathroom in Unit 2. Sheet EP1 Provide ADAAG Compliant Tub. Autumn Wollmann |Deputy Director Willdan Engineering |Comprehensive. Innovative. Trusted. 1440 E. Missouri Ave, Suite C170 | Phoenix, Arizona 85014 T. 480.787.5526 | F. 602.870-7601 |C. 480.404.8069 awollmann@willdan.com |
||
06/26/2023 | Fire New Construction | REQUIRES RESUBMIT | Provide written responses to all review comments: -Indicate the building will be provided with fire sprinklers per IFC 903.2.6 or how you meet one of the exceptions. -Indicate the building will be provided with a building fire alarm per IFC 907.2.6, 907.2.61 or how you meet the exceptions. john.vincent@tucsonaz.gov 5203495581 |
||
06/07/2023 | PDSD Application Completeness | REVIEW COMPLETED | |||
06/07/2023 | Site Engineering | REVIEW COMPLETED | Legacy Passed by SSHIELD1 |