Permit Number: T22CM05446
Parcel: 12509107A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM05446
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2022 Site Engineering NOT REQUIRED
12/12/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
12/09/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM05446

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the structural calculations proving that new equipment will adequately supported by the existing construction.

BUILDING REVIEW COMMENTS:
Denied
1. Some of the comments have been addressed and reference pages that have not been provided. Provide all missing pages from the construction drawing set.
2. The cooking narrative has not been provided that was previously requested.
3. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG. No accessible seating has been provided at the bar area.


MECHANICAL REVIEW COMMENTS:
Approved

ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved

If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/12/2022 Fire New Construction REQUIRES RESUBMIT Building plans will not be approved until DP22-0181 is approved

Questions:
Jennifer Peel-Davis
Tucson Fire Department
Fire Plans Examiner
Fire Inspector I, II and Fire Alarm Plans Examiner
Jennifer.Peel-Davis@Tucsonaz.gov
Desk: 520-837-7033
11/16/2022 Site Zoning REQUIRES RESUBMIT ZONING REVIEW TRANSMITTAL



FROM: PDSD Zoning Review



PROJECT: T22CM05446 – DP22-0181

5602 E Broadway Blvd. – C-1

TI Zeman’s Lounge – (2nd Review)



TRANSMITTAL: November 16, 2022



This site is located in C-1 Zone (UDC Article 4.7.20) Food Service w/alcoholic beverage service as an accessory use. (UDC Table 4.8-4), subject to Use Specific Standards 4.9.4.M.1 & 5, 4.9.13.O, 4.9.4.V.1, 3, & 5-9, 4.9.4.C.3, and 4.9.13.O are met.

Zoning has reviewed the building plans for compliance with DP22-0181 and although the plans appear to match until the DP is approved Zoning cannot approve this plan.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/10/2022 Commercial Plumbing REVIEW COMPLETED
11/10/2022 PDSD Application Completeness REVIEW COMPLETED