Permit Number: T22CM05446
Parcel: 12509107A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM05446
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/23/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
01/14/2023 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM05446

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
DENIED
1. Provide the structural calculations proving that new equipment will adequately supported by the existing construction.
NOTE: The comments are not being addressed and the previous drawings are just being resubmitted. Do not resubmit until comments have been addressed.


BUILDING REVIEW COMMENTS:
DENIED
1. Some of the comments have been addressed and reference pages that have not been provided. Provide all missing pages from the construction drawing set. NOT COMPLIED
2. The cooking narrative has not been provided that was previously requested. NOT COMPLIED
3. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG. No accessible seating has been provided at the bar area. NOT COMPLIED
NOTE: The comments are not being addressed and the previous drawings are just being resubmitted. Do not resubmit until comments have been addressed.


MECHANICAL REVIEW COMMENTS:
APPROVED


ELECTRICAL REVIEW COMMENTS
APPROVED


PLUMBING REVIEW COMMENTS:
APPROVED


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
01/19/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05446 – DP22-0181
5602 E Broadway Blvd. – C-1
TI Zeman’s Lounge – (3rd Review)


TRANSMITTAL DATE:‎January 19, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Zoning has reviewed the building plans for compliance with DP22-0181 and although the plans appear to match until the DP is approved Zoning cannot approve this plan.

If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
01/23/2023 Fire New Construction REVIEW COMPLETED
01/05/2023 PDSD Application Completeness REVIEW COMPLETED