Permit Number: T22CM05347
Parcel: 12217003B

Review Status: Approved

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM05347
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2022 Commercial Plumbing APPROVED
11/28/2022 Commercial Plumbing APPROVED Water review
11/15/2022 External Reviewers - SAFEBuilt APPROVED Activity Number: T22CM05347

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. No egress plan is provided. Provide a thorough egress plan.
2. At least 5% of the dining surfaces are required to have mobility features. Provide calculations of the required amount of accessible seating and indicate the locations. Additionally, ensure that surfaces are properly dispersed throughout the structure. Section 226.1 and 226.2 of the 2010 ADAAG.
3. There are tables and chairs that appear to be blocking an egress door. Please relocate this equipment to ensure proper clearance for egress.
4. There is an insufficient amount of exit signage provided. Provide exit signage in the kitchen area in accordance with Section 1013.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance.


PLUMBING REVIEW COMMENTS:
Denied
1. The sinks behind the service counters do not drain into the grease line. There is the possibility for these sinks to experience grease laden waste. Connect these sinks to the grease line.
2. Provide grease interceptor sizing calculations.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
11/28/2022 Fire New Construction APPROVED Restamp Required
10/31/2022 Site Engineering APPROVED
10/31/2022 Site Zoning APPROVED
11/28/2022 Site Zoning APPROVED requires restamp
11/28/2022 Site Zoning APPROVED Restamp Required
11/28/2022 Bldg Permits - Post Review Express REVIEW COMPLETED
11/26/2022 Fire New Construction REVIEW COMPLETED Resolve building comments

john.vincent@tucsonaz.gov
5203495581
11/28/2022 Fire New Construction REVIEW COMPLETED requires restamp
11/28/2022 Fire New Construction REVIEW COMPLETED restamp required, please stamp newest plan set