Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.4
Permit Number - T22CM05239
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | Please submit a complete set of plans with the updated corrections to sheet P1.0 | ||
01/09/2023 | Commercial Electrical | REQUIRES RESUBMIT | Re-stamp required. | ||
01/05/2023 | Commercial Mechanical | REQUIRES RESUBMIT | Resolve the conflicting schedule of operation for the proposed exhaust fan shown in the Fan Schedule and item #10 of the Plumbing Plan Notes. The exhaust fan shall run during periods of occupancy. [Second comment: The current version of sheet P1.0 has deleted the exhaust fan that was included in previously approved plan set. The installation of the exhaust fan addressed the previous comment.] [Previous comment: Spaces in which factory-built recirculating hoods tested in accordance with UL 710B are installed are considered to be kitchens and shall be ventilated per Section 403.3.1.1, IMC 2018. The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual cooking appliance (e.g. Unox oven and Turbo Chef oven). Reference: Section 507.1, exception 2, IMC 2018.] | ||
01/05/2023 | Commercial Plumbing | REQUIRES RESUBMIT | The Equipment Schedule on sheet P1.0 still shows the new hand sink draining indirectly to the floor sink. [Initial comment: Plumbing fixtures that receive or discharge liquid waste (e.g. hand sinks) shall be directly connected to the sanitary drainage system. Clarify the apparent contradiction of item 3 of the Plumbing Plan Notes and the Sanitary & Vent Riser Diagram. Reference: Section 301.3, IPC 2018.] | ||
01/09/2023 | External Reviewers - Willdan | REQUIRES RESUBMIT | Re-stamp required. | ||
01/09/2023 | Fire New Construction | REQUIRES RESUBMIT | Re-stamp required. | ||
01/09/2023 | Site Zoning | REQUIRES RESUBMIT | Re-stamp required. | ||
12/19/2022 | PDSD Application Completeness | REVIEW COMPLETED |