Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM05163
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/23/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
11/23/2022 | Commercial Mechanical | REQUIRES RESUBMIT | The existing heat pump, HP-1, is operating about 29% below the design air flow but is delivering an acceptable outside air flow rate. Have the engineer evaluate the situation and provide a course of action. Reference: Section 403.3.1.5, IMC 2018. | ||
11/22/2022 | PDSD Application Completeness | REVIEW COMPLETED | AIR BALANCE REPORT |