Permit Review Detail
Review Status: Requires Resubmit
Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Permit Number - T22CM05107
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/12/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/12/2024 | Air Balancing/Commissioning Report (Deferred Submittal) Express | REQUIRES RESUBMIT | The air balance report shows that EF-55 is specified to exhaust 100 CFM but is actually exhausting 55 CFM. Submit the report to the mechanical engineer for resolution prior to resubmitting the air balance report. Reference: Section 403.3.1.5, IMC 2018. | ||
| 12/12/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |