Permit Number: T22CM05106
Parcel: 121080610

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM05106
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/27/2022 Commercial Plumbing APPROVED Water review
01/04/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
12/15/2022 External Reviewers - SAFEBuilt REQUIRES RESUBMIT Activity Number: T22CM05106/BLDG #1 T22CM05107/BLDG #2 T22CM05108/BLDG #3 T22CM05109/BLDG #4

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
APPROVED


BUILDING REVIEW COMMENTS:
APPROVED


MECHANICAL REVIEW COMMENTS:
CONDITIONALLY APPROVED
1. Provide make up air for laundry room in an approved manner, if the HVAC unit is providing make up air then it shall be interlocked to the dryers and noted as such sheet M101 (IMC2018,504.6) Complied
2. All HVAC unit's shall be labeled on the mechanical HVAC Plan (e.g. AC-1, AC-2 etc.). sheet M101 (IMC2018,106.3.1) Complied
3. Exhaust method ventilation shall operate continuous at all times. you are not clear when you say that there is an on/off switch for the bathroom exhaust fans, that you are using for ventilation of the units on note 5, tenants shall not have the option of turning the ventilation off. sheet M201 (IMC2018,405.1) Complied


ELECTRICAL REVIEW COMMENTS:
APPROVED


PLUMBING REVIEW COMMENTS:
DENIED
Second Plumbing Review:
1 thru 3 OK
4). SAME-Community Bldg. kitchen sinks need to discharge thru grease interceptor. -IPC 1003.1 ** Comment response states approval letter from utility authority was attached?**
5 thru 7 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
12/02/2022 Site Engineering REQUIRES RESUBMIT The associated development package must be approved before any combination permits can be approved.

Lianne Evans
lianne.evans@tucsonaz.gov
11/16/2022 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: T22CM05106, T22CM05107, T22CM05108, T22CM05109
Multi Family (2nd review)
6226 E LEE ST Zoning R-3

TRANSMITTAL DATE: November 16, 2022


Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


Comment: Zoning has reviewed the building plans for compliance with the associated Development Package DP22-0145 Zoning cannot approve the building plans until the DP is approved.


If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
12/12/2022 Fire New Construction REVIEW COMPLETED
11/10/2022 PDSD Application Completeness REVIEW COMPLETED