Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - T22CM05025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/08/2022 | Commercial Mechanical | APPROVED | |||
12/08/2022 | Commercial Plumbing | APPROVED | |||
12/08/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/07/2022 | Commercial Electrical | REQUIRES RESUBMIT | REf; Electrical Plans. This project is considered commercial. Please remove code references to the IRC and replace with 1017 NEC. Please indicate in detail the full scope of electrical work for each unit. Relocate breaker panels out of the bathrooms to a code compliant location. NEC 240.24, 408. Bathroom branch circuit to be dedicated to bathrooms only. NEC 210.11(C)(3). All replaced or modified branch circuit wiring and outlets shall comply with 2017 NEC art 210. Lighting shall comply with the 2018 IECC for energy usage. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 City of Tucson/Pima County Outdoor Lighting Code |
||
12/06/2022 | PDSD Application Completeness | REVIEW COMPLETED |