Permit Number: T22CM05025
Parcel: 11007087B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM05025
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2022 Bldg Permits - Post Review PENDING ASSIGNMENT
11/01/2022 Commercial Electrical REQUIRES RESUBMIT Provide sealed electrical plans. For clarity, please indicate the full scope of electrical work in detail. Ref; 2018 IBC section 107.1, 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements, City of Tucson/Pima County Outdoor Lighting Code
10/28/2022 Commercial Mechanical REQUIRES RESUBMIT The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing which new HVAC systems or equipment will be installed. New HVAC units will have to comply with Sections R403.1 and R503.1.2, IECC 2018 for efficiency, controls, and ductwork.
10/28/2022 Commercial Plumbing REQUIRES RESUBMIT The estimate of the scope of work is not adequate to obtain a permit to repair the fire damage. Provide drawings showing the plumbing fixtures that will be installed and specifications (e.g. fixture descriptions and manufacturer's model numbers) for those fixtures. If any piping (water supply, waste and vent piping) needs to be replaced, show that on the drawings.