Permit Number: T22CM04954
Parcel: 133110190

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - T22CM04954
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/27/2023 Commercial Electrical REQUIRES RESUBMIT Provide plans and evidence on the plans that the proposed exterior lighting fully complies with the Outdoor Lighting Code. See section 104 for plan submittal requirements.

Provide site lighting plans with the following information on the plans/lighting lumen calculations;

1 Provide a complete luminaire schedule indicating shielding type (Unshielded or Fully Shielded) for each type of luminaire. Indicate lamp output color temperature (402.1). See DEFINITIONS Chapter 2.

2 Include the Garden area lighting if the area is not fully enclosed. And indicate if the Garden area is fully enclosed or not.

3 See table 401.1, INDICATE the lighting area and option used.

4 Provide calcs for total lumens allowed and total lumens proposed per acre for all lighting, Full Cut Off and Unshielded per table 401.1.

5 Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2.

6 Specify any exceptions used.

7 Curfew lighting controls If applicable.

Do not confuse the Outdoor Lighting Code with the IECC.

Ref; 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code (OLC), 2018 IBC sec 107.2.1. 2018 IECC.
02/14/2023 PDSD Application Completeness Express REVIEW COMPLETED