Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - T22CM04808
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
12/07/2022 | External Reviewers - SAFEBuilt | APPROVED | restamp required | ||
12/09/2022 | Site Engineering | APPROVED | restamp required | ||
12/29/2022 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
12/29/2022 | Commercial Plumbing | REQUIRES RESUBMIT | The revised Level 1 Water Supply & Gas Floor Plan on sheet P1.1 shows the water meter located within 5-feet of the building and the RPBP located within the building. The water meter will be located at the property line as shown on the civil drawings. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water and directly after the water meter for buildings that have food service facilities. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf | ||
12/20/2022 | Fire New Construction | REVIEW COMPLETED | restamp required |