Permit Number: T22CM04751
Parcel: 11006080A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - T22CM04751
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2023 Commercial Building APPROVED
01/12/2023 Commercial Mechanical NOT REQUIRED
01/12/2023 Commercial Plumbing NOT REQUIRED
01/24/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/20/2022 Commercial Electrical REQUIRES RESUBMIT Replacing wiring and or installing branch circuiting requires design and engineering. Also code knowledge... 2017 NEC art 210. The lighting replacement requires compliance with the 2018 IECC.

Receptacles must be replaced with Tamper Resistant type. NEC art 406.12.

Circuit breaker panels must be relocated to a code compliant location. NEC 240.24, 408.17.

This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
12/12/2022 PDSD Application Completeness Express REVIEW COMPLETED