Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - T22CM04751
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/24/2023 | Commercial Building | APPROVED | |||
| 01/12/2023 | Commercial Mechanical | NOT REQUIRED | |||
| 01/12/2023 | Commercial Plumbing | NOT REQUIRED | |||
| 01/24/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/20/2022 | Commercial Electrical | REQUIRES RESUBMIT | Replacing wiring and or installing branch circuiting requires design and engineering. Also code knowledge... 2017 NEC art 210. The lighting replacement requires compliance with the 2018 IECC. Receptacles must be replaced with Tamper Resistant type. NEC art 406.12. Circuit breaker panels must be relocated to a code compliant location. NEC 240.24, 408.17. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
||
| 12/12/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |