Permit Number: T22CM04751
Parcel: 11006080A

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.4

Permit Number - T22CM04751
Review Name: COMMERCIAL REVIEW - FULL v.4
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/29/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/29/2023 Commercial Electrical REQUIRES RESUBMIT Please address the following electrical plan review comments and provide a written response.

No written response found addressing the electrical plan review comments.

Electrical concerns not addressed. Previous Electrical plan review comments;




01/11/2023

12/20/2022

Replacing wiring and or installing branch circuiting requires design and engineering. Also code knowledge... 2017 NEC art 210. The lighting replacement requires compliance with the 2018 IECC. Receptacles must be replaced with Tamper Resistant type. NEC art 406.12. Circuit breaker panels must be relocated to a code compliant location. NEC 240.24, 408.17. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
05/26/2023 PDSD Application Completeness Express REVIEW COMPLETED