Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.3
Permit Number - T22CM04602
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/17/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
04/17/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. The previous plan review comments are not addressed; Provide full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. Indicate shielding for the exterior luminaires in the luminaire schedule, Full Cut-Off or Un-Shielded. Indicate in the lighting plans whether or not a Special Inspection is Required. Section 104.2.2, 106.2. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2012 Tucson/Pima County Outdoor Lighting Code. There was no response letter found in the re-submittal. |
||
04/14/2023 | PDSD Application Completeness | REVIEW COMPLETED |