Permit Number: T22CM04577
Parcel: 13614001H

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - T22CM04577
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/01/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Indicate the conductor sizes, quantity and types for the replacement service secondary feeders. It is not the utility company’s responsibility to replace 3 phase electrical service secondary conductors as noted on plan sheet E1.

Ref; 2018 IBC section 107.2.1, 2017 NEC.
07/25/2023 PDSD Application Completeness REVIEW COMPLETED