Permit Number: T22CM04501
Parcel: 132131090

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04501
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/24/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/24/2023 External Reviewers - SAFEBuilt PENDING ASSIGNMENT
02/24/2023 Fire New Construction PENDING ASSIGNMENT
02/24/2023 Site Engineering PENDING ASSIGNMENT
02/24/2023 Site Zoning PENDING ASSIGNMENT
02/24/2023 PDSD Application Completeness REQUIRES RESUBMIT Activity Number: T22CM04501/NEW QUICK TRIP

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
Approved with the following comments: Anchor bolts connecting the roof framing members to the top of masonry wall needs to be embedded a minimum 7" and a minimum 1/2" diameter (provided).


BUILDING REVIEW COMMENTS:
Denied
Sheet N101 - Provide area (SF) of this new enclosed room and updated occupancy load calculation. What is the revised actual area (SF)?
Provide site plan that captures this revision of this new room. Previous sheet C100 shows 6 feet dimension to curb while revision A110 shows 8 feet masonry wall at this location.
Sheet A101 – Label this room. What is the name of this room? A621 finish schedule and room missing.
What is the ventilation method for this new enclosed room in accordance with 2018 International Mechanical Code section 401.2?


MECHANICAL REVIEW COMMENTS:
N/A


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
N/A


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov