Permit Number: T22CM04440
Parcel: 106060140

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - T22CM04440
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/29/2022 Commercial Electrical APPROVED
12/19/2022 Commercial Structural APPROVED
12/19/2022 Fire New Construction APPROVED
12/19/2022 Site Zoning APPROVED
01/23/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/23/2023 Commercial Plumbing REQUIRES RESUBMIT Clarify the installation of the hydromechanical grease interceptor. The specified grease interceptor requires the installation of a vented flow control device at the inlet of the interceptor, a vent downstream of the interceptor and a cleanout downstream of the interceptor. In addition, the 3-compartment sink requires indirect waste connections for each of the three sink compartments. [Initial comment: Verify if an existing grease interceptor is currently in place to prevent the discharge of fats, oil, and grease into the public sewer. If a grease interceptor is not in place, show how the public sewer is to be protected from harmful discharges. Reference: Section 1003.1, IPC 2018.]
12/19/2022 Commercial Mechanical REVIEW COMPLETED
12/19/2022 PDSD Application Completeness Express REVIEW COMPLETED
12/19/2022 Site Engineering REVIEW COMPLETED