| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/22/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. Previous electrical review comments not addressed. 1 Is the Auto Gate, Temp GFI’s, Welding Receptacles, in the scope of work? If yes than include the wiring methods in the plans. If not in the scope, please address this with a note on the electrical plan. 2 Please review previous electrical review comments. Please include all plans and documents and response letter with the next submittal. Ref; 2018 IBC section 107.2.1, 2017 NEC. |
||
| 06/08/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |