| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/18/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/18/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 The registrant seal is expired. 2 As per the previous plan review electrical comment entered on 6-22-2023. It was requested to enter a note in the electrical plans as to what is not included in the scope of work for this permit. (New Office)?Please comply. 3 Provide a Grounding Electrode System for panel ‘B’, NEC 250.58. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
||
| 06/03/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |